Suitably rated fuses of the types listed below should
be used between the battery and load or charge circuits, placed as close
as possible to the battery. Fuses need to be sized based upon the length
of time the maximum current will occur taking into account surge ability
of the inverter or other devices.
Currents need to be 10% to 20% lower than fuse
ratings to avoid nuisance fuse blowing.
Also inverter efficiency needs to be considered. eg.
if this is 85% at high load a 3 kW AC load would draw 3450 W from the DC
battery, (ie. 288 A @ 12 V; 144 A @ 24 V).