Isolation Switches

DC Isolation Switches

These are used between high voltage DC PV arrays and grid-connect inverters. They are located adjacent to the inverter and are required to provide a means of manually isolating the entire PV array during system installation or any subsequent maintenance.

The switch must be rated for system voltage (1.15 x string open circuit voltage Voc) and current (1.25 x string short circuit current Isc).

DC isolators can be provided with 600mm long MultiContact cables and connectors.

This then allows the entire DC side of the PV installation to be completed by making only plug & socket connections. Thus eliminating the possibility of wiring error or accidental exposure to dangerously high DC voltages during installation.

Note: A PV array is unusual in that it cannot be turned off - terminals will remain live at all times during daylight hours. It is important that all junction boxes and switchgear is suitably labelled.

Double pole On/Off switches.

 

DC rated for switching under load.

 

IP66 weatherproof rated polystyrene enclosures

 

               PV-SW3/E

 

Supplied in three versions:

  • Mounted in enclosure with approved labelling (PV-SW3/E) 1000 VDC,16 A ;

  • Mounted in labelled enclosure with terminal rail to connect up to three strings and fitted with knockouts (PV-SW4/E) 1000 VDC, 25 A;

  • Mounted in labelled enclosure and fitted MultiContact connectors for connection to PV array output cables and with 600mm MultiContact cables for connection to inverter (PV-SW5/EMC) 1000 VDC,16 A.

      PV-SW4/EW4/E

PV-SW5/EMC

PV-SW3/E

2 pole DC isolator switch in enclosure

PV-SW4/E

2 pole DC isolator switch in enclosure with glands

PV-SW5/EMC

2 pole DC isolator switch in enclosure with MC connectors e/p & 600mm long MC cables on o/p

 

AC Isolation Switches

 

These are required to provide a means of manually isolating the AC supply to a grid-connect inverter.

 

Two AC isolation switches need to be provided between the inverter and the point of connection to the supply.

 

 

One adjacent to the inverter and one adjacent to the consumer unit (Only one is needed if in the same room). The one adjacent to the consumer unit must be readily accessible and capable of being locked in the off position only. Switches must be double pole and suitably labelled.

Double pole single throw switch lockable in the off position only, mounted in enclosure. Rated: 230/400 Vac.

AC-SW1

4 pole 20A AC lockable isolator switch in enclosure

AC-SW2

4 pole 32A AC lockable isolator switch in enclosure

 

G59 Protection Relays

These are usually required for grid-connect inverter systems greater than 5kW in size and provide additional protection. They are located between the inverters and the point of connection to the supply. POA.

OfGem Approved Ac kWh Meters

These are used to accurately record wind or PV generation. OfGem approved to allow ROC’s or other payments for on-site generation to be claimed. They are located between the inverters and the point of connection to the supply. Include pulsed output for connection to displays.

ME-160

Single Phase kWh meter (analogue)

ME-162

Single Phase kWh meter (digital)

ME-171

Three Phase kWh meter (digital)

up to the top

Home

Contact Us

Prices & Special Offers

About Wind & Sun

News

Renewable  Energy Systems

System Sizing

Wind Power

Solar Power

Inverters

Generators

Batteries

Lighting

Pumps & Fountains

Solar Models & Kits

Books

Balance of System Components

Exhibitions

Product Data

Projects

Links

 

 

Contact us

How to Order

Catalogue

Prices

 

Copyright Wind and Sun Ltd - no reproduction without express written permission, unless for personal use.