Sizing Cables
Very high currents can flow in cables connecting inverter to the batteries and between the batteries. Cables must be adequately sized to suit the maximum current drawn by the inverter. Low resistance links and tight connections are essential to maintain even use of a battery bank.
In order to minimise the voltage drop between battery and inverter, and so maintain inverter efficiency, cables should be kept as short as possible and be sufficiently sized.
Recommended sizes (2m long) are:
| Conversion of American Wire Gauge to Metric | ||
| Size AWG | Amp Rating per single conductor | Area mm² |
| 20 | 7 | 0.52 |
| 18 | 10 | 0.82 |
| 16 | 15 | 1.31 |
| 14 | 20 | 2 |
| 12 | 25 | 3.31 |
| 10 | 40 | 6.68 |
| 8 | 65 | 8.37 |
| 6 | 95 | 13.3 |
| 4 | 125 | 21.15 |
| 2 | 170 | 33.62 |
| 1 | 195 | 42.41 |
| 1/0 | 230 | 53.5 |
| 2/0 | 265 | 67.43 |
| 3/0 | 310 | 85 |
| 4/0 | 360 | 107.2 |
| 250 | 405 | 126.7 |
| 300 | 445 | 152 |
| 500 | 620 | 253.4 |
| 750 | 785 | 300.66 |
| 1000 | 935 | 506.7 |
| Battery to Inverter Cable Size (2m long) | |||
| Inverter Wattage | Battery Voltage | ||
| 12 V | 24 V | 48V | |
| 150 W | 10 mm² | 6 mm² | - |
| 250 W | 16 mm² | 6 mm² | - |
| 500 W | 35 mm² | 10 mm² | - |
| 1000 W | 50 mm² | 25 mm² | - |
| 1500 W | 50 mm² | 35 mm² | - |
| 2000 W | 70 mm² | 50 mm² | - |
| 2500 W | 95 mm² | 70 mm² | 50 mm² |
| 3000 W | - | 95 mm² | 50 mm² |
| 3500 W | - | 95 mm² | 70 mm² |
| 4500 W | - | - | 70 mm² |
To calculate an acceptable size of wire to do a particular job, it is necessary to know the wattage or amperage of the appliance, it's distance from the battery, and the system's voltage
In general most 12 V lighting and appliances will work on voltages as low as 11-11.5 V. But if possible, wiring should be sized so that losses are less than 2% ie a 0.25 V drop.
(See Table 2.)
The following equation is useful in choosing the required wire:
R = E / I x L
R = Resistance of wire in Ohm/m
E = Maximum allowable voltage drop in the wiring in volts
I = Current drawn by appliance in amps = Wattage/Voltage
L = Length of wire of the complete circuit in metres (count twice - both in & out).
For Example:
If a 60W (60/12 = 5A) appliance needs to be situated 10m from a 12V battery and the maximum allowable voltage drop is 2% (0.25 V):
R = 0.25 Volt / [(5 Amps)x(20m)] = 0.0025 Ohm/m.
Therefore resistance of the wire should be less than 0.0025 Ohm/m. Looking at Table 1 this means that 6 mm² wire or thicker must be used. The thicker the wire the better the efficiency.
Voltage drop becomes less of a problem with higher voltage systems.
Table 1
| Cross Sectional Area | Maximum Current Rating (Amps) | Resistance | |||
| Enclosed Cable In Conduit Or Trunking | Cable Clipped Direct To Open Surface | Ohm / metre | |||
| mm² | Twin | 3-Core | Twin | 3-Core | Per Core |
| 1.0 | 11 | 9 | 12 | 10 | 0.018 |
| 1.5 | 13 | 12 | 15 | 13 | 0.012 |
| 2.5 | 18 | 16 | 21 | 18 | 0.0074 |
| 4.0 | 24 | 22 | 27 | 24 | 0.0046 |
| 6.0 | 30 | 27 | 35 | 30 | 0.0031 |
| 10.0 | 40 | 37 | 48 | 41 | 0.0018 |
| 16.0 | 53 | 47 | 64 | 54 | 0.0012 |
| 25.0 | 60 | 53 | 71 | 62 | 0.00073 |
| 35.0 | 74 | 65 | 87 | 72 | 0.00049 |
Table 2
Maximum length (in m) of cable from power source to load for less than 2% voltage drop. (For a 12 V system.) (For 24 V systems cables can be twice as long; 240 V wiring can be 20 times as long)
| Cable Size (mm² cross-sectional area) | ||||||||||||
| Amps | 1 | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 75 | 100 |
| 1 | 7 | 10.91 | 17.65 | 28.57 | 42.86 | 70.6 | 109.1 | 176.5 | 244.9 | - | - | - |
| 2 | 3.53 | 5.45 | 8.82 | 14.29 | 21.4 | 35.3 | 54.5 | 88.2 | 122.4 | 171.4 | - | - |
| 4 | 1.76 | 2.73 | 4.41 | 7.14 | 10.7 | 17.6 | 27.3 | 44.1 | 61.2 | 85.7 | 130.4 | - |
| 6 | 1.18 | 1.82 | 2.94 | 4.76 | 7.1 | 11.7 | 18.2 | 29.4 | 40.8 | 57.1 | 87 | 117.6 |
| 8 | 0.88 | 1.36 | 2.2 | 3.57 | 5.4 | 8.8 | 13.6 | 22 | 30.6 | 42.9 | 65.25 | 88.2 |
| 10 | 0.71 | 1 | 1.76 | 2.86 | 4.3 | 7.1 | 10.9 | 17.7 | 24.5 | 34.3 | 52.2 | 70.6 |
| 15 | - | 0.73 | 1.18 | 1.9 | 2.9 | 4.7 | 7.3 | 11.8 | 16.3 | 22.9 | 34.8 | 47.1 |
| 20 | - | - | 0.88 | 1.43 | 2.1 | 3.5 | 5.5 | 8.8 | 12.2 | 17.1 | 26.1 | 35.3 |
| 25 | - | - | - | 1.14 | 1.7 | 2.8 | 4.4 | 7.1 | 9.8 | 13.7 | 20.9 | 28.2 |
| 30 | - | - | - | - | 1.4 | 2.4 | 3.6 | 5.9 | 8.2 | 11.4 | 17.4 | 23.5 |
| 40 | - | - | - | - | - | 1.8 | 2.7 | 4.4 | 6.1 | 8.5 | 13 | 17.6 |
| 50 | - | - | - | - | - | - | 2.2 | 3.5 | 4.9 | 6.9 | 10.4 | 14.1 |
| 100 | - | - | - | - | - | - | - | 1.7 | 2.4 | 3.4 | 5.2 | 7.1 |
| 150 | - | - | - | - | - | - | - | - | - | 2.3 | 3.5 | 4.7 |
| 200 | - | - | - | - | - | - | - | - | - | - | 2.6 | 3.5 |
Copyright of Wind & Sun Ltd - no reproduction without express written permission unless for personal use. Registered in England & Wales, Company No.3403803 VAT Number GB 448 5458 14 Registered Office: Humber Marsh,